DTC B1442: Air Inlet Damper Control Servo Motor Circuit [12/2019 - 10/2022]: Procedure
- CHECK FOR DTC
- Check for DTCs.
Body Electrical > Air Conditioner > Trouble Codes
Result
Result Proceed to DTC B1497 is not output A DTC B1497 is output B
Result:
B
GO TO DTC B1497. Refer to DTC B1497: Communication Malfunction (Bus Ic) [12/2019 - 10/2022]
Result:
A
See step 2
- Check for DTCs.
- CHECK FOR DTC
- Check for DTCs.
Body Electrical > Air Conditioner > Trouble Codes
Result
Result Proceed to DTC B1441, B1446 and B1448 are not output A DTC B1441, B1446 or B1448 is output B
Result:
B
REPLACE NO. 1 AIR CONDITIONING RADIATOR DAMPER SERVO SUB-ASSEMBLY. Refer to DISASSEMBLY [12/2019 - 10/2022]
Result:
A
See step 3
- Check for DTCs.
- CHECK NO. 1 BLOWER DAMPER SERVO SUB-ASSEMBLY (INSTALLATION CONDITION)
- Check that the No. 1 blower damper servo sub-assembly is installed correctly.
OK
No. 1 blower damper servo sub-assembly is installed correctly.
Result
Proceed to OK NG
Result:
NG
REINSTALL NO. 1 BLOWER DAMPER SERVO SUB-ASSEMBLY. Refer to REASSEMBLY [12/2019 - ]
Result:
OK
See step 4
- Check that the No. 1 blower damper servo sub-assembly is installed correctly.
- CHECK NO. 1 BLOWER DAMPER SERVO SUB-ASSEMBLY (MOTOR, LINK, DAMPER)
- Check for a wire harness caught between the links of the motors and dampers.
OK
No wire harnesses are caught between the links of the motors and dampers.
Result
Proceed to OK NG
Result:
NG
REMOVE PINCHED WIRE HARNESS
Result:
OK
See step 5
- Check for a wire harness caught between the links of the motors and dampers.
- INSPECT AIR CONDITIONING HARNESS ASSEMBLY
- Disconnect the No. 1 air conditioning radiator damper servo sub-assembly connector.
- Disconnect the No. 1 blower damper servo sub-assembly connector.
- Measure the resistance according to the value(s) in the table below.
Standard Resistance
Tester Connection Condition Specified Condition A-6 (STE2) - B-3 (sigB) Always Below 1 Ω A-5 (STE1) - B-2 (sigA) Always Below 1 Ω A-8 (M-) - B-5 (M-) Always Below 1 Ω A-7 (M+) - B-4 (M+) Always Below 1 Ω A-4 (GND) - B-1 (GND) Always Below 1 Ω A-6 (STE2) or B-3 (sigB) - Other terminals and Body ground Always 10 kΩ or higher A-5 (STE1) or B-2 (sigA) - Other terminals and Body ground Always 10 kΩ or higher A-8 (M-) or B-5 (M-) - Other terminals and Body ground Always 10 kΩ or higher A-7 (M+) or B-4 (M+) - Other terminals and Body ground Always 10 kΩ or higher Result
Proceed to OK NG
Result:
NG
REPLACE AIR CONDITIONING HARNESS ASSEMBLY. Refer to DISASSEMBLY [12/2019 - 10/2022]
Result:
OK
See step 6
- CHECK BLOWER ASSEMBLY (DAMPER)
- Remove the No. 1 blower damper servo sub-assembly.
Refer to DISASSEMBLY [12/2019 - ]
- Operate the dampers by hand.
OK
The dampers are easily operated by hand.
Result
Proceed to OK NG
Result:
OK
REPLACE NO. 1 BLOWER DAMPER SERVO SUB-ASSEMBLY. Refer to DISASSEMBLY [12/2019 - ]
Result:
NG
REPAIR OR REPLACE BLOWER ASSEMBLY
- Remove the No. 1 blower damper servo sub-assembly.